Annex 4f - Guidelines for (stand) construction at RAI

Stand guidelines
These guidelines are intended to ensure that stands are safe and welcoming, addressing matters such as floor and wall heights and improved accessibility for visitors with disabilities.
A separate electricity supply connection must be requested for each stand. Electricity supply connections must not be shared between stands. For detailed electrical regulations, see ANNEX 4b - 'Electrical Regulations for (Stand) Construction at RAI'.
Stands, fittings and exhibits
Stand walls and freestanding items must remain within the stand boundaries and must not extend beyond them. Exhibits must also remain within the stand boundaries, including during demonstrations. This also applies to sound and lighting, both of which must be directed into the stand, not towards aisles or other stands. Hazardous parts, such as moving, sharp or protruding components, must be effectively guarded, and heavy goods must be secured against falling or toppling.
Any extension beyond the stand boundaries requires prior approval from the Event Organiser and must not cause inconvenience or nuisance to other exhibitors.
Stand wall height
The standard stand wall height is 250 cm (including any raised floor), matching the standard ‘ready-to-exhibit’ stand construction. Stand structures up to 300 cm high are permitted only if the rear surfaces of partition walls above 250 cm are neatly finished in a neutral style, without branding or promotional material.
Tall or non-standard (stand) structures
Non-standard stand wall heights affect climate control at RAI and must be reported to the Organiser, who must then coordinate with RAI. Trusses above the stand area must not be suspended more than 700 cm above floor level (depending on the hall). Air supply units and safety facilities, including fire hose reels, must remain unobstructed at all times.
For non-standard structures that may present a hazard, or that would normally be accessed only by instructed or appropriately trained persons, RAI reserves the right to commission an independent expert assessment (at the organising Party’s expense) and, where appropriate, require the Parties to sign an indemnity in favour of RAI.
Stands with an upper storey or other elevated structures may be erected only with the organiser’s written permission. These non-standard structures must also comply with the Buildings (Living Environment) Decree (Bbl), formerly the Building Decree 2012.
Following the organiser’s approval, a permit must also be requested from the RAI Permitdesk (permits@rai.nl); see ANNEX 3a - 'RAI Permits Manual', within the given deadline in this document.
This applies, for example, to:
- Stands with an upper storey;
- Stages/catwalks (60 cm high and above);
- Grandstands; and
- Scaffolding (60 cm high and above).
Ceilings or roofs on (stand) structures
Such stands may be fitted with ceilings. Freely suspended ceilings (attached solely to the building’s roof structure) are permitted following approval by the relevant RAI department and RAI’s designated installer, who must install the suspension wires; see ANNEX 4e - 'RAI Rigging Manual'.
The climate control system supplies air through jet diffusers high in the hall, from where it descends and spreads across the hall floor. As a result, cooling or heating may not function optimally in stands fitted with ceilings and/or large purpose build meeting rooms in the halls. Advise can be obtained from the RAI Real Estate Department (realestate@rai.nl).
Enclosed stands
These are stands enclosed on all sides, including the roof, preventing smoke from reaching the Convention Centre ceiling directly. Stands with solid ceilings must not obstruct fire protection systems. Fire detection (smoke detectors), sprinkler systems, smoke and heat exhaust ventilation and evacuation alarm systems must be able to operate as freely as possible.
If a (stand) structure needs to be enclosed on all sides, an application must be submitted to RAI Safety&Security (safety@rai.nl).
Additional measures apply (at the Organiser’s or Exhibitor’s expense); see also ANNEX 2a - 'RAI Fire Safety Regulations'. These stands must be monitored by a temporary fire detection and alarm system providing full coverage in accordance with NEN-EN 2535 and connected to RAI’s fire detection and alarm system.
Floors at the RAI Convention Centre
The floors in the Convention Centre halls have an asphalt finish. Owing to differential settlement, the floors in the Europa Complex (Halls 1 to 7) are not entirely level. Any problems this causes on site may be reported to the RAI Exhibitor Desk or the Event Manager on duty (eventmanagement@rai.nl).
Floor coverings in Halls 1 to 12 may be secured to the asphalt floor using residue-free double-sided tape.
The floors in the Convention Centre’s meeting and conference rooms, lounges, foyers and Elicium 1 and 2 are finished with carpet, marble or natural stone. Floor coverings for stands and aisles, for example, must not be fixed directly to stone floors using double-sided tape. A raised stand floor or rubber underlay must be installed first. ANNEX 4d - 'RAI Floor Load Limits' sets out the rules for using the marble floor.
Usage of special floor coverings (concrete slabs, sand, gravel, etc.) requires written permission from RAI Real Estate (realestate@rai.nl). Plastic sheeting must be laid over the floor before any such materials are brought in.
Further information on floor types, coverings and load limits in the various areas of the Convention Centre is provided in ANNEX 4d - 'RAI Floor Load Limits'.
Floors for (stand) structures
Raised floors are recommended for stands with water and compressed air pipes and/or extensive electrical or ICT cabling; the stand builder can advise on this. The following general guidelines apply to raised stand floors:
- Stand floors must be laid within the stand boundaries;
- The height measured from the building floor to the top surface of the raised floor must not exceed 15 cm; and
- The sides of raised floors must be enclosed and neatly finished. Sharp edges and corners must be avoided; bevelled edges may be used where appropriate.
Stand floors higher than 15 cm are not readily accessible to people with disabilities. A ramp is therefore strongly recommended. The following guidelines for stand floors adjoining an aisle have been drawn up to improve access for visitors with disabilities or reduced mobility (MIVA), including wheelchair and walking frame users, people with walking difficulties, and blind or partially sighted visitors:
- For raised stand floors, it is strongly recommended that the outer edge has a matt finish in a colour contrasting with the aisle and any ramp colour. The ramp must fit within the stand boundaries;
- Where a stand floor is less than 5 cm above the aisle, a bevelled edge or ramp at least 1 m wide is sufficient for wheelchair or walking frame access. The bevelled edge must have a matt finish in a colour contrasting with the remaining floor edges;
- For stand floors up to 20 cm above the aisle, a ramp at least 1 m wide is strongly recommended for visitors with disabilities or reduced mobility:
- Up to 10 cm high: at least 1 × 1 metre; and
- Up to 20 cm high: at least 1 × 2 metres.
- Where a stand floor is 22 cm high, steps must be provided at all main access points. The first and last steps should be marked with a contrasting line or contrasting dots (approximately 50 mm in diameter);
- A handrail is not required on a ramp where the stand floor is less than 20 cm above the aisle. If a handrail is installed, it must be positioned 80–100 cm above the ramp and follow its slope. The handrail must be easy to grip (round or oval) and should preferably have a light, matt finish contrasting with a dark rear wall. The handrail end must not project freely, and a single-sided handrail must be positioned on the wall side;
- The edges around a ramp must not be sharp, and floor junctions must provide a smooth transition without high thresholds. A ramp in the corner of a stand must have an upstand approximately 4 cm high along its length to prevent users from rolling off; and
- Where the floor level difference exceeds 60 cm, the stand is regarded as a stage and a permit is required. Contact the RAI Permitdesk (permits@rai.nl) or consult ANNEX 3a - 'RAI Permits Manual'.
The floor beneath the stand must not be painted and must be left clean after the stand has been dismantled. The exhibitor will be charged for the removal of any residue.
Large or heavy stand components
Large or heavy stand components must be installed first during the build-up period. Arrange this with the Event organiser during the stand allocation process.
Corporate social responsibility and stand construction
RAI aims to make the events industry more sustainable and encourages exhibitors and stand builders to minimise the environmental impact of transport, construction and exhibiting, including through the use of:
- Electric transport;
- LED lighting;
- Reusable materials;
- RAI modular stand construction; and
- Digital communication instead of paper handouts.
Stand breakdown / dismantling
Stands may be cleared and dismantled, and goods removed from the building, during the breakdown period(s) published for Exhibitors by the Event Organiser:
- Breakdown starts no later than 2.5 hours after the event closes. The exact timing is agreed separately for each event. Stands and structures must not be dismantled during these 2.5 hours. Hand-carried goods may, however, be removed;
- Everyone must wear a visible badge during breakdown;
- Everyone must also wear safety footwear and have a safety helmet to hand during breakdown. The helmet must be worn when the red warning light is on;
- Boxes and crates may be placed in aisles only after the aisle floor coverings have been removed. Exhibitors near goods entrances may be required to clear their stands earlier, as notified by the Event Organiser;
- After the dismantling period, the stand space must be left clean and free of adhesive tape. Any goods, stand construction materials or waste remaining in the Convention Centre or on its grounds after the published breakdown period will be removed, stored and/or disposed of at RAI’s discretion, at the expense and risk of the Party concerned;
- If tape from carpet tiles or similar materials is left on the hall floor after the exhibition, the Party will be charged for its removal; and
- For safety reasons, the electricity supply to stands will be disconnected immediately when the Event closes on the final Event day. Please ensure that equipment is switched off in good time.
Additional stand construction rules for individual Events
At some Events, Exhibitors may obtain written dispensation from the Organiser to depart from the stand construction rules. The Organiser must seek advice from its RAI Account Manager on this matter and, if approved, record the agreed arrangements in its own participation terms and conditions. The Exhibitor must consult the Event Organiser in advance to establish whether departures from the rules are permitted and under what conditions.
This Annex 4f 'Guidelines for (Stand) Construction at RAI'
is attached to the Accommodation Regulations,
was prepared by RAI Event Management and
was last updated on 1 August 2026.