logo

Annex 4c - RAI Regulations for the Use of Batteries and Battery-Powered Equipment

1.1

Battery packs and batteries are essential to the success of Events. They are used in equipment and machinery during build-up and dismantling, but also during the Events themselves, where their operation is often demonstrated.

On-site power generation is not permitted; for example batteries or battery packs may not be used to replace fixed power connections at the stand.

There are several types of battery packs and batteries; in particular, the last item in the list below, the lithium-ion battery, entails risks, including fire hazards. It is essential that Parties are aware of these risks and take the appropriate precautionary measures.

When using battery packs and batteries correctly, Parties must comply with the following basic conditions:

  • Battery packs and batteries must bear a CE-marking;
  • Fire detection must be present at the location and connected to a fire alarm;
  • When battery packs and batteries are not being charged, charging cables must be removed; and
  • Smoking and open flames are not permitted within 10 metres of battery packs and batteries.
1.2Lead/sulphuric-acid batteries are used in cars as starter batteries, in forklift trucks as traction batteries, in fire and intruder alarm systems and in large emergency power systems. Lead/sulphur batteries are not a fire hazard. Excessive charging current or excessive discharge may damage the battery; thermal runaway is not possible with this type of battery. During charging, this type of battery releases small quantities of hydrogen gas which, provided the space is adequately ventilated, do not pose any risk. Charging in unventilated spaces is therefore not permitted.
1.3Nickel/cadmium batteries (NiCd) are used in various types of rechargeable equipment, such as torches, measuring equipment and emergency lighting. NiCd battery cells are hermetically sealed; under normal use, no liquids or gases are released. Nickel/cadmium batteries are not a fire hazard, and thermal runaway is not possible with this type of battery. The materials in the battery are non-combustible; at most, the plastic casing may burn.
1.4

The collective term lithium-ion batteries refer to a number of different battery technologies. These battery packs and batteries contain chemicals (salts or polymers) that contain lithium. These chemicals have in common that they are unstable and readily decompose as a result of excessive charging current, excessive discharge, mechanical damage or external heat.

A fire in a lithium-ion battery cell is a chemical decomposition reaction that releases a large amount of energy. The heat released causes an increasing proportion of the cell contents to decompose and may even cause a decomposition reaction in adjacent cells. This phenomenon is referred to as thermal runaway.

To keep the measures manageable, battery packs and batteries have been divided into four groups: small, medium-sized, large and very large battery packs or batteries. The capacity of the lithium-ion battery packs and batteries to be used is classified as follows:

  • Small (> 0 tot < 3 kW), for example laptops or telephones;
  • Medium-sized (> 3 tot < 20 kW), for example an electric bicycle or a sweeper;
  • Large (> 20 kW tot < 150 kW), for example an electric car; and
  • Very large (> 150 kW), for example an ESS (energy storage system), together with the location of use, determines whether use and/or charging is permitted.
1.5

Conditions for the use of small, medium-sized, large and very large battery packs.

This classification sets out at which locations battery packs and batteries are permitted and whether charging (and discharging) of battery packs and batteries is permitted at that location. This approach has been adopted because research shows that charging (and discharging) battery packs and batteries is the point at which the fire risk is greatest.

See Table 1. Overview of locations where different sizes of battery packs and batteries are permitted and may be charged:

table 1

* permitted only in spaces with a sprinkler installation,
** permitted only if the surface area is < 2 m 2 and the distance to combustible materials is > 2 m,
*** permitted only if the distance to the façade or to combustible materials is > 10 m,
**** permitted only if the distance to the façade or to combustible materials is > 10 m and the space is fitted with a sprinkler installation.

At the request of our Health & Safety department, you must be able to provide proof of the size (capacity) of the lithium-ion battery or battery pack you are using.

See Table 2. Examples of products with battery packs and batteries.

Table 2. EVs = (fully) electric vehicles, ESS = energy storage systems.
1.6

Small battery packs and batteries are always present throughout RAI, for example laptops, telephones and power banks. These battery packs and batteries may also be charged in most RAI locations, provided sprinklers are present in the offices and meeting rooms.

During an exhibition, charging (or discharging) small battery packs and batteries is never permitted, because there is high occupancy by Visitors who are not familiar with the building.

1.7

Medium-sized battery packs and batteries are permitted throughout RAI. However, charging entails greater risks and is not permitted during Events or in offices and meeting rooms. These locations have high occupancy and a relatively high fire load; given the increased fire risk during charging, charging is therefore not permitted there.

Kitchens and storage areas have a lower fire load or occupancy, so charging is permitted there, provided a certified sprinkler system is present.

During the build-up and dismantling of an Event, charging is permitted provided sufficient distance is maintained from the façade and combustible materials.

Specific measures for small and medium-sized battery packs:

  • The battery pack or battery must bear a CE-marking;
  • Fire detection must be present in the compartment and connected to a fire alarm;
  • When the battery pack or battery is not being charged, charging cables must be removed; and
  • Smoking and open flames are not permitted within 10 metres of the battery pack or battery.
1.8

Large battery packs and batteries, for example electric cars, are not permitted in the meeting rooms and offices of the Convention Centre because the fire load and occupancy are relatively high and the compartments are low. Lithium-ion battery packs and batteries burn quickly, creating a large volume of smoke in a short time. In high spaces such as exhibition halls, there is a buffer providing more evacuation time. This situation is not the case in offices and meeting rooms.

In other spaces, large battery packs and batteries are permitted, provided rapid detection is present (exhibition halls) or a sprinkler system is present (kitchens, storage areas and car parks).

Large battery packs and batteries may be charged only in exhibition halls during build-up or dismantling, and in storage areas and car parks, provided sprinkler systems are present in all these spaces. This is due to the increased risk associated with charging and the low occupancy in these spaces. On the site, a distance of at least 10 m from the façade of the building must be maintained when charging battery packs and batteries.

If the lithium-ion battery pack or battery is large (20 kW to 150 kW), additional specific measures apply in and around the Convention Centre in addition to the basic conditions.

Specific measures for large lithium-ion battery packs (20 kW to 150 kW).

General:

  • Do not place charging stations for electric vehicles near an escape route or emergency exit;
  • In the event of a fire alarm, the charging stations in the relevant zone must be switched off;
  • Install impact protection in front of the charging stations or place the charging stations where impact is impossible;
  • Where possible, install charging infrastructure as close as possible to the entrance or exit of the building;
  • Connect a control to the fire detection system that switches off the charging points simultaneously when fire is detected in a zone;
  • Provide a charging-cable bracket next to the charging station;
  • Do not place combustible objects next to or on the charging stations; and
  • Visually inspect the charging cables regularly.

Personnel:

  • Use only approved (IEC 62893) and undamaged charging cables for charging;
  • Position the charging cable during charging in such a way that:
    • Vehicles cannot drive over it;
    • Another vehicle cannot become caught on it and damage the cable; and
    • Persons cannot trip over or become caught behind the charging cable.
  • Ensure that an electric vehicle with a fault or possible damage is placed outside the building at a distance of at least 10 metres until the vehicle has been inspected by a qualified technician;
  • Charging takes place during regular build-up times;
  • Charging takes place in an acceptable location: not in front of emergency doors or on yellow routes;
  • Continuous supervision must be present during charging. This means that someone is always nearby; that person may also be carrying out other work at that location;
  • Charging at night is not permitted;
  • RAI reserves the right at all times to impose additional conditions or to refuse the request; and
  • In the event of identified breaches, RAI Amsterdam will unplug the equipment from the socket.
1.9

Very large battery packs and batteries will mainly be battery packs and batteries stored outside the Convention Centre, for example neighbourhood batteries and ESS units. These battery packs and batteries may therefore be stored on the site if a distance of ten (10) metres from the façade is maintained (not under a canopy). At this distance, these battery packs and batteries may also be charged and discharged. In view of the great height of the exhibition halls in the Convention Centre, these battery packs and batteries may also be placed there, but here too a distance of ten (10) metres from the façade of the building and combustible materials must be maintained.

The car parks and storage areas are lower, so these battery packs and batteries are permitted only if a distance of ten (10) metres from the façade and combustible materials is maintained and the space is sprinklered.

A very large battery pack or battery may not be charged or discharged in the Convention Centre. This is permitted only on the outdoor site at a distance of ten (10) metres from the façade and combustible materials.

If the lithium-ion battery pack or battery is very large (> 150 kW), additional specific measures apply in and around the Convention Centre in addition to the basic conditions;

Specific measures for very large lithium-ion battery packs (> 150 kW and above)
Energy storage systems (ESS) contain batteries of 150 kW and above. The consequences of a battery fire involving these capacities are significant and separate measures must be observed:

  • Preferably use new batteries in the ESS;
  • The entire space must be watertight, drifting-snow-tight, mouse-proof, fire-resistant and vandal-resistant;
  • An ESS must, within fire compartmentation, have a fire resistance of at least 60 minutes to prevent fire propagation. The doors must have fire and smoke resistance equivalent to that of the adjoining walls;
  • An automatic extinguishing system in the compartment is desirable;
  • A lightning protection system that complies with IEC 62305-3 level 3 or 4;
  • A smoke and heat extraction system must be installed for each battery room to discharge smoke and heat to the outside in the event of thermal runaway;
  • Ventilation grilles must extend at least above the highest battery;
  • Climate control must be present;
  • Smoke detectors must be present in all separate compartments, with onward notification to the RAI control room (24/7 alarm receiving centre);
  • The battery compartment must be fitted with a 3” Storz coupling to which the fire brigade can connect a fire-water supply;
  • The ESS must always be accessible by a fire engine and must have an emergency stop facility on the outside;
  • A zone of 2 metres around the ESS must be maintained at all times so that work can be carried out safely;
  • If the ESS is situated within 10 metres of a public road, effective impact protection is recommended;
  • A fire-water supply with a capacity of at least 800 l/min must be present within 40 metres of the ESS;
  • An ESS must be identifiable from the outside; the following texts/symbols must therefore be displayed on the outside of an ESS:
    • “Neighbourhood battery” or “Energy storage system”, followed by the installed capacity in kWh;
    • Labelling in accordance with the CLP standard (Li-ion, electrocution, fire and toxicity);
    • The type of batteries installed;
    • Name of the grid operator/owner; and
    • Emergency telephone number.

This Annex 4c 'RAI Regulations for the Use of Batteries and Battery-Powered Equipment'
is attached to the Accommodation Regulations,
was prepared by RAI Safety & Security and
was last updated on 1 August 2026.